GENERAL
 
What are the differences between the WeatherDuck and the Goose?
 
The main difference is that the WxDux has no built-in network capability, and must be connected to a host PC running its supplied client software via a serial port, whereas the WxGoos contains a built-in Web server and Ethernet port which allows it to connect directly to the network and produce a web page without any need for an external host PC or client software.
 
What are the most popular remote sensors?
 
Remote Temperature
For monitoring "hot" spots and other trouble areas

Water Sensor
Check for water leaks

Door Contact Sensor
See if a door is open

Remote Temp / Air Flow / Humidity
Climate monitoring in remote locations
Remote Sensor Wiring
 
What is the difference between analog and digital sensors?
 
Analog
Analog sensors connect through the analog inputs. These sensors are either a dry contact or provide a 0 to 5VDC signal. On the web interface, they show up as "IO" sensors and have a value 0 to 99.

Digital
These connect to digital input ports and communicate though a serial protocol. Digital sensors are auto-detected by the climate monitor. Measurements from these devices are graphed and report in the appropriate units.
Remote Sensor Comparison
 
Where is the log data stored?
 
WxGoos Series I / II
Log data is stored in RAM until it is recorded to an on-board DataFlash memory chip. Once the memory is full, new data is written over the old. The Logs page will tell how much data can be stored before it is overwritten.

WeatherDuck
The data is logged every minute into an Excel spreadsheet file on the system running WeatherDuck Server software. Each month the old file is dated and closed, and a new one created.
 
What is a friendly name?
 
It is a more descriptive name for the device, generally the location of a remote temperature sensor, or the type and location of an IO sensor. To change a friendly name, edit the text and select save changes.
 
SERVICES
 
What does SNMP mean?
 

SNMP is the Simple Network Management Protocol. It provides a way for network devices to communicate. In the protocol there is a manager device that uses SNMP to find out the status of devices on the network. These devices are called agents.

Normally, the manager makes a request to an agent, and the agent responds to this request. For example the manager asks the Goose for its temperature, the unit reads the temperature and sends this back to the manager.

The exception to this is SNMP traps. A trap is an alert sent by an agent to the manager about some abnormal condition. For instance, if the temperature on the unit leaves an acceptable range, the Goose can send an SNMP trap to the manager.

 
Why can''t I telnet into my Goose?
 

The login for telnet uses the username/password for Admin account access. If these fields are blank you will not be able to login. These values can be entered on the Configuration page.

Sometimes there is a problem with spaces being added to an input line. Try hitting backspace a few times before typing in the login username and password.

WxGoos Series I Only: A machine running a Windows OS works best. If using unix press control + enter when inputting a line.

 
PORTS
 
What can I attach to the Analog Inputs?
 
These are 0 to 5 volts DC analog inputs with built-in loop current (provided through a 100K ohm pull-up resistor). Typical applications are magnetic door sensors, occupancy sensors, liquid sensors (conductance), or any other sensor using a dry-contact switch (no power supplied by switch).

For analog signal sensing, a relatively low-impedance (<10K ohm) source is needed to overcome the pull-up resistor.

CAUTION: The sensor must provide a negative-ground signal and it needs to be connected to the "C" terminal. Positive signal voltage should be connected to a numbered terminal. If the polarity is wrong it could damage the Analog Input ports.
 
How do I connect the wires to the Analog Inputs on a Goose?
 

Each terminal has an upper and lower opening. The wire inserts into the larger, bottom opening. The top one is used to open a spring-loaded jaw that holds the wire in place. To insert the wire:

  1. Strip at least 1/2" of insulation from the wire ends.
  2. Insert a small screwdriver into the upper opening.
  3. Pry upwards with the screwdriver. (You should see the jaw open in the lower opening)
  4. Insert the wire into the bottom opening
  5. Plug out the screwdriver, allowing the jaw to close, gripping the wire.
CAUTION: The negative-ground signal should to be connected to the "C" terminal. Positive signal voltage should be connected to a numbered terminal. If the polarity is wrong it could damage the Analog Input ports.
 
How do I connect the wires to the Analog Inputs on a Duck?
 

The analog ports are a screw-type terminal block.

  1. Strip insulation from wire ends. (minimum 1/2")
  2. Use a small flat-blade screwdriver to open each terminal.
  3. Insert the sensor wire into the terminal underneath the screw.
  4. Tighten the screw again to grip the wire into place

CAUTION: The negative-ground signal should to be connected to the "C" terminal. Positive signal voltage should be connected to a numbered terminal. If the polarity is wrong it could damage the Analog Input ports.

 
What about the phone jacks on your devices?
 

These jacks are actually RJ-12 ports. The RJ-12 has six conductors while phone jacks will have either two or four. All of the sensors, except the RTAF and RTAFH, can operate with a four-conductor RJ-11 connector. (The RTAF/RTAFH devices require additional power to operate, which is delivered via the extra two conductors on the full 6-wire RJ-12 jack.) Remote digital sensors can be attached to these jacks. Each sensor has a built-in 64 bit unique address. The sensors can have an aggregate cable length of up to 600'' total. Using appropriate splitters up to 16 digital sensors are supported.

Note: Not all climate monitors have Digital Sensor ports.

 
How are the digital sensors wired?
 
They are wired with Cat-3 cable using six wires and a RJ-12 connector. If the wiring needs to be changed, the connections must be straight-through (no cross-overs). For best results, avoid running the cable near high voltage or high current equipment. A snap-on ferrite choke installed on a sensor cable to help with electrical interference.
 
CONSOLE
 
How many climate monitors can I monitor at once with Watchdog Console?
 
It should be able to monitor up to 200 units.
 
What kind of load will WatchDog Console put on my network?
 
The load is minimal.
 
Does console run as a Windows service?
 
Yes.
 
POWER
 
Why monitor power usage with a current transformer in a power strip?
 
If your power load is approaching the limit, the breaker could trip and bring down the entire cabinet full of equipment. The CT can spare IT managers midnight or weekend trips to the office to reset breakers by letting them know if they are operating near the limit.
 
Don''t the equipment placards tell you how much current each device consumes?
 
Not reliably. The current consumed varies widely depending on how many accessories are installed and is generally the maximum the unit is rated for.
 
Other than buying your product, how can I tell how much current a power strip is using?
 
An electrician powers the equipment down, inserts a break-out box and reads the current using a clamp-on ammeter. This costs about $65 per power strip and causes about 30 minutes of down time.
 
Once I have a electrician measure the power, why should it change?
 
Power usage changes substantially as equipment is added and removed. One additional piece of equipment could put the breaker right up against the trip point.
 
What is power factor?
 
In AC circuits, loads that are not purely resistive can cause voltage and current to be out of phase. This causes the apparent power (which you are billed for) to be greater than the actual power used. This can be corrected by adding reactance to a system to make it purely resistive. Such measures, however, are generally reserved for large scale operations.
 
What''s the difference between Apparent Power and Real Power?
 
Apparent Power is the calculation of volts times amps which is mathematically equivalent to current squared times impedance. Real power is current squared times the resistive component of your load''s impedance.
 
What does RMS mean?
 
The acronym means Root-Mean-Squared. This means the DC voltage which would generate the same heat in a resistor as the AC voltage you have. The usefulness is that you know the actual power being consumed and not an estimate as in peak-to-peak calculations. RMS takes much more computing power but is more useful.
 
What about peak voltage?
 
Peaks are troublesome because they trip surge protectors and you come to work with power-down servers and wonder why. The graphs will show peaks coming and going as a trend.
 
So if I use your power strip, I get an alarm if I get close to the circuit breaker trip value?
 
Yes, the unit e-mails or pages you if you set up the alarms properly. Some units have audible alarms.
 
What else should I know about power?
 
Watch the graphs. One user had chronic server shutdowns in the early morning hours. The graphs showed a morning power sag caused brownout conditions and server shutdown.
 
What about 3 phase power?
 
You will see the voltage and current of each phase. You can easily balance the phases when you know what each power strip is using.
 
Why are the graphs so important in power monitoring?
 
Power changes. Voltage sags and peaks. The graphs tell the story. Taking occasional readings doesn''t show trends.
 
WXGOOS
 
How do I setup my WxGoos Series I?
 

We recommend that you set up your goose by directly connecting it to a computer using the following steps:

  1. Power the unit using the supplied power supply.
  2. Ensure that the green power indicator is on. Soon after powering on, the green Ethernet status indicator will blink three times.
  3. Connect the unit to a local system using a cross-over cable.
  4. The orange Link indicator will turn on if a good link has been established. If the indicator does not light, then check the connections and/or try a new cross-over cable.
  5. Configure the network card on your PC with these settings:

    IP Address: 192.168.123.100
    Subnet Mask: 255.255.255.0
    Gateway: 192.168.123.1

    Note: More details are provided in another portion of this FAQ
  6. Open a web browser and direct it to http://192.168.123.123
 
How do I setup my WxGoos Series II?
 

We recommend that you set up your goose by directly connecting it to a computer using the following steps:

  1. Power the unit using the supplied power supply.
  2. Ensure that the green power indicator is on. Soon after powering on, the green Ethernet status indicator will blink three times.
  3. Connect the unit to a local system using a cross-over cable.
  4. The orange Link indicator will turn on if a good link has been established. If the indicator does not light, then check the connections and/or try a new cross-over cable.
  5. Configure the network card on your PC with these settings:

    IP Address: 192.168.123.100
    Subnet Mask: 255.255.255.0
    Gateway: 192.168.123.1

    Note: More details are provided in another portion of this FAQ
  6. Open a web browser and direct it to http://192.168.123.12
 
How do I configure my computer to connect to the WxGoos Series I / II?
 
  1. Click on the Start button.
  2. Select the Control Panel. If the control panel is not an option you may need to choose Settings -> Control Panel.
  3. Click on the Network Connections icon.
  4. You should now see one of more icons that represent network cards installed on your system. Choose the network card you connected the Goose to and right click it and select Properties.
  5. Find and double-click Internet Protocol (TCP/IP).
  6. This opens a window that shows your current network card settings. It should like similar to the window shown. Make a note of the current settings, so that they can be restored later.
  7. Ensure that "Use the following IP address" is selected and enter the following settings in the appropriate fields.

    IP Address: 192.168.123.100
    Subnet Mask: 255.255.255.0
    Gateway: 192.168.123.1

  8. ou can leave the DNS fields blank. Click the OK button on the TCP/IP window to save the changes. Then click OK on the Local Area Connection window to finalize the process.
 
What are the various tabs on a goose?
 

Sensors
View sensor measurements along with graphs of historic data. Observe still images from webcams.

Alarms
Use this page to set alarm thresholds. Choose who gets alerts and how they will be notified.

Logging
Graph your choice of sensors and time span. Download log files and clear them when needed.

Display
Edit friendly names for internal and remote sensors. Set interface display options like temperature units (°C / °F).

Config
Configure features and services including SNMP, email, access accounts and IP webcams.

 
How do I update firmware on a WxGoos Series I?
 

These instructions can also be found in the firmware zip file.

  1. Download the latest firmware for your device from: www.itwatchdogs.com/downloads.shtml
  2. Connect the unit with a CROSS-OVER cable to the computer that will be used for the update. Trying to update a unit not directly attached to a computer MAY damage the unit and WILL VOID YOUR WARRANTY.
  3. Change your Network Interface Card''s (NIC) settings to the following:

    IP Address: 192.168.123.100
    Subnet Mask: 255.255.255.0
    Gateway: 192.168.123.1

  4. If you have enabled the built-in Windows firewall or any third-party firewall, disable it before continuing.
  5. Extract the zip file to an easy to find location (ie a folder on your desktop or at the root level of your hard disk)
  6. Open the folder in Windows Explorer.
  7. Double-click on the ''updater.exe'' file and follow the on-screen instructions.
  8. If everything works properly, the device should be available for use about two minutes after the update is complete.
  9. Restore the NIC''s previous settings once the firmware update is complete.

Should you run into any trouble while updating, please DO NOT power-cycle your Goose. Contact ITWatchdogs at:

Phone: 512-257-1462
E-mail: support@itwatchdogs.co

 
We lost the password to our Goose how can we recover it?
 

Please email us with the unit''s Goose series (I or II) atsupport@itwatchdogs.com

We will send you a new password so you can access the unit to change the password.

If you aren''t sure of the series, this link should help.

 
What are the requirements to run your supported webcams?
 
  • WeatherGoose unit running firmware version 2.51 or higher
  • Computer with Internet Explorer 6.x or higher with Active enabled
  • Windows XP/2000/Me
 
Your units support 16 external sensors, but most of them don''t have this many RJ-12 ports, how can I connect 16 of them?
 
We sell a 5 port and 16 port splitter to add additional ports. Multiple 5 port splitter can be chained to get up to 16.
 
What webcams can I use with the Goose?
 

We have tested the ones we sell and those in the following list. Other webcams may work, but are not supported.

D-Link DCS: 900, 910, 950/950G, 2000, 3220/3220G, 3410, 3420, 5300/5300G, 6620

Axis: 205, 206

LinkSys: WVC200

Panasonic Webcams

Note: IP-based Webcams are not supported by WeatherDuck.

 
How do I get the MIB for the unit?
 
The MIB for the unit can be found in two places. In the header of the unit web page, under Alternate Formats, is a link to the MIB. A copy of the MIB is also included in the firmware zip file.
 
I need the OID''s for the unit.
 
Download the firmware zip file for the version you are running. It contains a CSV file with the list of OID''s.
 
Is there a way to turn the buzzer off remotely on a WxGoos Series I?
 

The Test Alarms feature can be used to turn the buzzer off remotely. The following step will lead you through this process.

  1. Go to the Alarms tab.
  2. Scroll down to the Test Alarms section.
  3. Pick one of the internal sensors from the Sensors drop-down.
  4. From the Alarm State drop-down, choose Buzzer.
  5. Select Clear from the Trap Type drop-down.
  6. Click on the Test button.
  7. The buzzer should turn off in a few seconds.
 
I just noticed that the firmware on the Web page and the firmware on the SuperGoose LCD are different.
 
This is not a problem, the web firmware is for the web server in the goose, but the firmware on the LCD is the firmware on the processor so they should be different.
 
What does the LCD on my SuperGoose I/II display?
 
The LCD will display the sensors whose checkboxes are set on the Logging page.
 
Why does it sometimes take a while for my goose to cycle between tabs on the goose web page?
 
The web server on the goose is limited, and if there is higher traffic on the site, or if you try to change between tabs rapidly it will slow down while it processes the requests.
 
How can I pull graphs off my goose with an HTTP request?
 

The following is a guideline for using the graph CGI query:

timerange
A negative value of -1 means all data points available. A positive values means the last N seconds of data. Values under 100 are too small to be effective and ignored by the unit.

width
This argument refers to width of the image rendered. The maximum value is 416. Values less than 1 or greater than 416 are undefined and result in undefined behavior

height
This argument refers to the height of the image rendered. The maximum value is 300. Values less than 1 or greater than 300 are undefined and result in undefined behavior.

device
This argument includes ALL sensors from a given device into the graph. The device value must be a valid 16 character ID.

sensor-
Notice the dash after the sensor label. This argument includes a sensor from a device into the graph. The sensor- value must be a valid 16 character device ID followed by the 0-based index of the sensor of intereste. Sensor offsets to non-existant sensors result in undefined behavior.

Notes: Mixing device and sensor- arguments in the same graph CGI querymay produce undefined results.

Examples
Query all data points for all sensors in main weathergoose device

http://www.weathergoose.com/graph.bmp?width=256&height=150&timerange=-1&device=010307640B00006A

Query last 15 minutes of data points for light level sensor in main weathergoose device

http://www.weathergoose.com/graph.bmp?width=256&height=150&timerange=900&sensor-=010307640B00006A3

Query all data points for relative humidity and sound level sensors in main weathergoose device

http://www.weathergoose.com/graph.bmp?width=256&height=150&timerange=-1&sensor-=010307640B00006A1&sensor-=010307640B00006A4

 
Can I have my goose turn on/off the outlets on a PowerEgg II if an alarm is tripped?
 
You can use 3rd party software like IP Sentry or you could write a script to provide the glue logic that parses the Goose''s
XML and then sends the correct HTTP POST transaction to the Goose to turn on or off the controllable relay based on
parsed sensor values.
 
SENSORS TAB
 
How often does the sensors page refresh?
 
Every 60 seconds, for faster refreshes please hit the browser''s refresh button. Camera images refresh along with the page.
 
How are sensors grouped on this page?
 
By device, so all the three sensors in a Remote Temperature / Air Flow / Humidity sensor with show up on one graph,
and the one sensor in an remote temperature will show up in one graph.
 
What other formats on the page are supported?
 

PDA
A small version of the Sensors page, used on PDA''s and cell phones.

WAP (WxGoos Series I)
A special version of the Sensors page, used by WAP-enabled cell phones.

XML
The current data, along with device information, displayed in XML.

MIB
Check on this link to download the MIB for the Goose. Used in SNMP.

 
My graphs are not displaying correctly. I get dots instead of lines, breaks or the scale is completely wrong.
 

This error is most commonly caused when the graphing routine cannot recognize or interpret a data point correctly.

This can be caused if the Goose is having trouble connecting to an NTP server. Check the time shown on the Goose''''''''s
web page in the upper-left corner; if the time shown is incorrect, or the unit says no NTP service is available, this is likely to
be the source of the problem. If your goose cannot access an external NTP server (due to, for example, being behind a
firewall), there is software available from AdjustTime.com that will allow a PC server to act as an NTP service.



At present, we are still investigating the other possible causes, but in the meantime there is a simple workaround.

  1. Download your log data (only if you want to keep the data; otherwise, you can skip this step).
  2. Clear the unit''s log history by going to the logs page, checking theclear log history box, then press the button
    marked save changes.
  3. Your graphs should come back in a few minutes, once the unit has accumulated sufficient new data to begin graphing again.
 
Can I change the graphs on the Sensors page on the Goose
 
No, this page cannot be modified by an end user.
 
LOGS TAB
 
How does the graph on the Logging page work?
 

Checkboxes let you select which sensors you want graphed. Use the Time Range drop-down to set the range of the
graph. The Y-axis shows the sensor values and the time is shown on the X-axis. The legend at the bottom shows relates
sensor name to color. Click the Update Graph button to generate a new graph.

On a unit with a LCD display, the checkboxes also control which sensors are displayed.

 
How do I download log data?
 
On the Logging page, select the "Click here to download raw log data" link. The log file is in CSV format and will be
called "log.csv". This download can take quite a while, if the logs are large.
 
What is the logging frequency?
 

The logging frequency tells the unit how often to record a measurement. A low frequency saves data more often,
but at a cost of fewer days of saved data. Once the logs are filled, new data overwrites the old data. The text under
the graph tells how long measurements can be logged before data is replaced.

WxGoos Series II
The logging frequency is fixed, one measurement every 60 seconds.

WxGoos Series I
The logging frequency can be set to 15 to 250 seconds. Aftering editing the value, make sure to click the Save Changes button.

 
How do I clear the log history?
 
To clear the log data, check the Delete Log History checkbox and click on the Save Changes button. In a few seconds the graphs should clear and graphing will resume in a few minutes.
 
I want to change the logging frequency but it is grayed out?
 
An account level of Control or Admin Access is required to change the logging frequency or delete the log data. It will grayed out if the current access level is not high enough. To change this, do the following:
  1. To change to Control access click on the Control tab. For Admin click on Configuration.
  2. Enter the appropriate username/password for the appropriate account.
  3. Click on the Logs tab and the Logging Frequency and Delete Log History checkbox should not longer be grayed out.
 
DISPLAY TAB
 
How do I change the unit of temperature?
 
Use the Temperature drop-down box to change the unit of measurement for temperature. Then select Save Changes to finalize the change.
 
My sensors are showing up as unplugged. What does this mean?
 

All the sensors are connected to a common serial bus. If one sensor goes down they may all go down if the bad sensor "jams" the bus or refuses to release it.

EM interference with the 1-wire signals could also be the cause. Check to see if the sensor cables are routed close to something that creates a lot of EM interference such as a generator, a large motor, or a large backup-battery charger.

Another source of interference is sensor wiring that runs parallel to the main power cables for any high current equipment such as an arc-welder, air compressor, or an HVAC unit.

Try rerouting the sensor wiring away from these sources to reduce interference. Another option is to attach a snap-on ferrite choke to the cable.

Check the environment the sensors are in to see if it is pushing them past their built-in limits. Temperatures below freezing can cause ice or condensation to form, creating shorts across the sensor terminals, making the sensor appear dead If the temperature exceeds the range of the sensor (-4° F to 122° F) it may show up as unplugged (WxGoos Series I only)

If the suggestions above don''t help then one of the sensors could be dead. Try disconnecting all sensors from the unit, then reconnecting them one at a time until you find the one that causes the problem. Once you have isolated the faulty sensor, disconnect it, and the other sensors should work normally.

Email support@itwatchdogs.com or call us for service and support options for the faulty sensor.

 
Why does the goose save unplugged devices?
 

The list of friendly names includes all devices that are attached to the unit as well as those that were. This way if a device is unplugged and reattached later, the settings for the device are restored. However, these unplugged sensors count toward the 16 external sensors limit.

If you need to remove these to make room for other sensors, then check the "Remove all unplugged devices" checkbox and click Save Changes.

 
ALARMS TAB
 
How do the alarms work?
 
The climate monitor compares the current reading against a threshold. An alarm trips if the reading passes the threshold. This causes the climate monitor to perform an action, like sending an email or SNMP trap.
 
How do I create alarms on WxGoos Series II?
 

The alarm thresholds are grouped by the device they are assigned to. There is a separate section for each device. An alarm threshold has the following:

Sensor Name: Sensor to check
Low/High Trip: Lower boundary or upper boundary
Threshold: Value to compare against
Action Checkboxes: Actions to perform when tripped



To set a threshold, use the drop-downs to select the sensor name and whether the threshold value is a lower limit and upper. The alarm trips if the current value is below a low trip, or above a high trip. Set checkboxes to tell what should happen on a trip. The E-mail and Traps boxes will give the corresponding address if you mouse over them. Click Save Changes to finalize.

If you need more thresholds for a device hit "Add New Alarm" in that section.

To get rid of a threshold, select the sensor name "(REMOVE ALARM)" from the drop-down and click Save Changes.

 
How do I set alarms on WxGoos Series I?
 
For each sensor there is a Low Trip, High trip and Alarm State. Use the low and high trips to set the acceptable range for the sensor. If the current value of the sensor goes below the Low Trip or higher than the High Trip, or the device is unplugged the alarm is considered tripped. When the value goes back into the acceptable range or the device is reattached, the alarm is cleared. To control how you will be notified of alarm trips and clears use the Alarm State drop-down. The choices are Email, SNMP trap, Buzzer( if the unit has one), or a combination of these. One notification is sent when the alarm is tripped and another notification is sent when the alarm clears. Set the alarm state to Disabled if you do not want to set an alarm for a sensor. Make sure to click Save Changes after adjusting the alarm settings.
 
What happens when an alarm trips?
 

The goose will send one email and/or trap when the value of the sensor exceeds the threshold, then another email and/or trap when the reading goes back into the norm.

Example: You set a high trip for temperature to 80°F. When the temperature rises to 81°F, a "tripped" alert is sent. Later, it falls to 79°F and another alert is sent. This is a "cleared" alert telling you that the sensor no longer past the boundary.

If the alarm is set to 80°F and the temperature is oscillating between 79-81°F this can result in large numbers of alerts being sent. To correct this, move the threshold a little past this range, to prevent the fluctuations from triggering excessively alerts. In this case you might want to adjust the threshold to 82°F or 83°F.

 
How do I test the alarms?
 

Note: It is a good practice to regularly test the alarms

Use the Send Test Email and Test SNMP Trap buttons.

WxGoos Series II: Bottom of Config > Monitoring page
WxGoos Series I: Bottom of Configuration page

Send test alert through the Test Alarms section (WxGoos Series I)

At the bottom of the Alarms page is the Test Alarms section. It''s used to send specific test alerts. The following instructions describe how to use this feature.

  1. Select a sensor to test from the Sensors drop-down.
  2. Choose the method of notification from the Alarm State drop-down.
  3. Use the Trap Type drop-down to pick between trip or clear.
  4. Click the Test button to send the notification.


Set a threshold exceeded by current conditons.

One method is to set a threshold that trips under the current conditions. For example, if the temperature is 75°F, then make an alarm threshold with a high trip of 70°F. The temperature exceeds the threshold, so the system will send an alert.
Note: Due to the nature of the system, you will not get a clear alert, if you now change the threshold to clear the alarm.

Water Sensor

Put the sensor in a container with water to trip an alarm. Let it dry to clear.

Note: If you aren''t receiving alerts, the Event Log is useful in troubleshooting.

 
What is the event log?
 

he Event log is a chronological list of events that have taken place on the unit. This is where errors, and warnings are listed as well as alarm notifications. The Event Log is also useful for debugging email and SNMP issues.

WxGoos Series II

The Event Log is located under the Config > Event Log Tab. You can adjust the level of detail using the checkboxes in Memory Syslog, the section below the Event Log.

WxGoos Series I

The Event Log is located on the Alarms page. The default logging level is Verbose. To change this use the drop-down box to select the logging level and then click Set Mode.

 
CONTROL TAB
 
What can I do under the control tab?
 
From this tab you are able to manipulate any control devices that might be attached to the system. For instance, a PowerEgg 2 would have the status of receptacles and buttons to turn them on and off.
 
CONFIGURATION TAB
 
How do I configure the network settings on WxGoos Series II?
 

You can edit these settings on the Config > Network page. This page is divided into two sections Network and Web Server. The Network section deals with Network and DNS configuration. The Web Server section is concerned with Services.

The Current Network Configuration shows what network settings are begin used and whether they come from DHCP or were entered by the user (Static). There are three configurations for the radio buttons, described below.

DHCP, DHCP for DNS

The unit gets the network setting (IP address, Subnet, Gateway) from DHCP and uses the DNS servers addresses also provided by DHCP. The climate monitor must be attached to a new network that supports this option. The input fields are ignored.

DHCP, Static DNS

The monitor get IP address, Subnet and Gateway through DHCP from the network. Enter the static IP address for Primary and Secondary DNS server in the input fields. The input fields for Network (IP, Subnet, Gateway) are ignored.

Static Network, Static DNS

The unit will use the static entries you provide for IP Address, Subnet Mask, Gateway, Primary and Secondary DNS Servers.

Use the Web Server section to configure services.

Protocols: Chose whether to allow HTTP, HTTPS or both (default)
HTTP Port: What port HTTP listens on (80 by default)
HTTPS Port: What port HTTPS listen on (443 by default)
Telnet Service: Turn on/off the Telent service

 
How do I configure the network settings on WxGoos Series I?
 

The main network settings are found on the Configuration page.

To assign the unit a static IP address, fill in the Static IP address field, Static Net Mask, and Static Gateway fields. Make sure the DHCP checkbox is unchecked if using a static IP address.

The next two drop-downs let you enable/disable Telnet and SNMP. The HTTP Services drop-down lets you choose if you want to allow HTTP, HTTPS, or both.

The last two input fields let you set the HTTP and HTTPS ports. The default port for HTTP is 80, and 443 for HTTPS.

 
How do I configure the NTP settings?
 

WxGoos Series II

This is configured on the Config > Admin page. The WxGoos Series II has two options for time-keeping. You can use the built-in Real Time Clock (RTC). Select "Manual - GMT" for Set Clock method. Enter and date and time. The RTC has power backup, so it can keep time even if power is disrupted.

The other option is to have the unit connect to a Time server through NTP. In this case, chose NTP Server under Set Clock method. Use "GMT to local" to enter the time zone offset (from GMT). Enter a primary and secondary NTP server.



WxGoos Series I

For the unit to know the date, it needs to be able to connect to an NTP server. The IP address for two servers can be entered. If these fields are left blank the unit will use the default addresses of 192.5.41.40 and 192.5.41.41. To adjust the time retrieved from the NTP server for time zone and/or Daylight Savings, use the "Time zone offset from GMT" field.

 
How do I setup the email?
 

Note: The Event Log is very useful in debugging email issues

Enter the address of the Email server in the SMTP Server field.

Give the unit a From address.

The unit can send email to up to 5 addresses. Enter these in the To fields. Using commas or semicolons to concatenate email address is not supported, so make sure to only enter one address per line.

The remaining fields are filled dependent on the Authenication method. Email servers have different requirements for authentication. The Goose supports ESMTP, POP3 and None (skip authenication).

None
If you don''t know which is required, start with None. Often, if you use None, the From address needs to have the same network or domain as the email server. Sometimes, the To address must also be in the same domain. Leave the POP3 Server and Username/Password blank.

ESMTP Auth
Leave the POP3 Server field blank. Enter values for the Username and Password that the email server will recognize. Set the SMTP Port to 465 to send an encrypted email via ESMTP/TLS (WeatherGoose Series II Only).

POP3

You need to fill in the POP3 Server and Port, along with Username/Password. In most cases, the POP3 Server is the same as the SMTP Server.

Hit the Save Changes button to confirm changes.

 
How do I setup the SNMP on WxGoos Series I?
 
Under configuration go to SNMP. The community string for traps can be set using the SNMP Trap Community String field. This only sets the community string for traps. Currently the unit only supports the "public" community string for SNMP requests. The unit can send SNMP traps to up to 4 addresses. Enter these in the SNMP Trap IP address fields.
 
How do I setup the user accounts?
 

Use the Name and Password section to control access to the unit.

There are three levels of access accounts, Admin, Control, and View-only

Admin

The highest account is Admin, which allows full read/write access to each page on the unit.


Control
The second level of access is Control. This allows access to the Sensors, Logs and Control tab. Control access also lets the user change the logging frequency (WxGoos Series I only) and delete the logs from the Logging tab.

View-only
The lowest access level is View-only. The user can view the Sensors and Logging page. At the View-only level, the user can not change the logging frequency (WxGoos Series I only) nor delete log history on the Logging tab.

 
How do I setup the webcams?
 

WxGoos Series II

  1. Make sure the Camera has an IP address that the Goose can reach.
  2. Use a browser to connect to the Goose.
  3. Go to the Config > Monitoring page.
  4. Near the bottom of the page is the Camera configuration section.
  5. Enter the IP address of the camera in the Camera IP Address field.
  6. Select the camera model using the drop-down list.
  7. Click on Save Changes to save the camera configuration

WxGoos Series I

The WxGoose Series I needs to be running firmware version 2.51 or higher for DLink 950/950G to work.

  1. Make sure the Camera has an IP address that the Goose can reach.
  2. Use a browser to connect to the Goose.
  3. Click on the Configuration tab.
  4. Scroll down to the bottom of the page to find the Camera Configuration.
  5. Enter the IP address of the camera in the Camera IP Address field.
  6. Select the camera model using the drop-down list.
  7. Click on Save Changes to save the camera configuration
 
What are the Device Info fields for?
 

Information from the fields in this section is displayed in the footer of each web page. This information helps identify the Goose and the person responsible for its maintenance.

Three of these fields correspond to SNMP objects. These are Contact Email (sysContact), Device Location (sysLocation) and Device Description (sysName).

Note: Since these map to SNMP objects, they can be read and set through SNMP commands as well as the web interface.

 
TROUBLESHOOTING
 
What should I do if I cannot get my WxGoos to display a web page?
 
  1. To minimize possible issues, it is best to debug the unit by connecting it directly to a PC through a cross-over cable.
  2. Check the connections to the unit and the network. The power and link indicators should both be on and stable. The activity light should blink periodically. If the power light is not on, check the connection on both ends. If the link light is out then check the network cable connections. A cross-over cable should be used for connecting directly to a computer and a straight-through should be used for connecting to a network.
  3. Ensure the network card settings are appropriate for the IP address of the unit. The recommended network settings for a unit at the default IP address are:

    IP Address: 192.168.123.100
    Subnet Mask: 255.255.255.0
    Gateway: 192.168.123.1

  4. Try to contact the unit using ping, telnet or ftp. For instance at the default IP address these commands would look like the following:

    ping 192.168.123.123
    telnet 192.168.123.123
    ftp 192.168.123.123

    If the unit is not at the default IP then the correct IP address would need to be substituted for the 192.168.123.123.

  5. If DHCP is enabled, the IP address for the unit may have changed. Check with the DHCP server to find out the current IP address for the unit.
  6. If the IP address of the unit was changed by DHCP or by the Configuration tab, make sure to use the new IP address to connect to the unit.
  7. WxGoos Series II: The default IP address (192.168.123.123) can be restored by holding down the IP Reset button for 20-30 seconds. WxGoos Series I: Even if the IP address was changed, the unit can still be reached at 192.168.123.123.
  8. If the unit is still unreachable, it may be on a different subnet, could be blocked by a firewall, or a proxy could be preventing access. Try connecting the climate monitor to another PC.

 
I can''t get emails from my goose, what should I do?
 

Check the Event Log for email errors. This may help diagnose the problem. You will probably need refresh the page several times to see all of the messages.

WxGoos Series II: Make sure all of the checkboxes are selected for email in Syslog.
WxGoos Series I: Make sure the logging level is set to Verbose.
Try a numeric IP address for the SMTP Server IP address (and POP3 IP address if used).

The unit needs a From address to send an email. This address may need to have the same domain as the mail server.

There should only be one email address in each To field.

Some email servers require the POP3 fields to be filled in. If POP3 isn''t required these fields should be left blank.

If an Exchange server is being used, then it needs to be configured to allow 3rd party emails. There is a checkbox for this purpose in the Exchange server configuration.

Sometimes Exchange is setup to only accept emails from a list of IP address. The Goose may need to be added to the list.

 
I have not been able to get a SNMP trap from the unit.
 

A SNMP manager must be configured to receive traps from the unit. Most SNMP programs have a database of traps, they are monitoring for. The possible traps that can be sent by the unit must be added to this database. Some programs can take the unit MIB and extract the trap information. With other programs the trap data has to be entered manually.

A CSV file is included in the firmware zipfile of version 2.53 and higher. The CSV includes the OID''s for the unit as well as the information for each trap. Below is a list of issues that might stop you from getting traps from the unit.

  1. See if there are errors in the Event Log.
  2. Not all SNMP software is able to receive traps. Check if the software can receive version the appropriate SNMP version of traps.
  3. Make sure the IP address configured on the unit, matches the IP address of the SNMP manager.
  4. Ensure that the Trap Community String on the unit, corresponds to the community string expected by the manager.
  5. On some SNMP software, you have to enable trap monitoring and SNMP requests.
  6. Check the Event/Error Log on the SNMP Manager. Sometimes there is a list of unsolicted/unknown traps.
 
WXDUCK
 
Stand-alone WxDux
 

The WxDux is a matchbox-sized device that plugs into the serial port of a server or other PC which contains a variety of environmental sensors. The WxDux is powered from the serial port, eliminating the need for an external power supply.

The sensors were picked based on accuracy and a history of use in industrial sensing applications. The temperature sensor, for example, is accurate to within 0.5°celsius. See the specifications sheet for all the sensor accuracies.

An internal microcontroller handles all communications with the external sensors, relieving the PC of any complex data-conversion processes. When the PC wants to know temperature, for example, it merely sends a "T" to the COM serial port and an ASCII text string containing the temperature reading is returned. Loading of the PC is minimized.

 
How is a web page created with the WxDux?
 
The supplied software creates Java server pages which are normally accessed through Port 8080. Each time you access the web page, the JSP program queries the WxDux for the latest data and builds the HTML code you see in a web browser.
 
What kind of a load does the WxDux software place on my PC?
 
The supplied software uses 30 megabytes of memory and runs as an NT service. We test on a 700MHz PC and when a web page request comes in, CPU usage shows about 2%. Every 60 seconds the software writes to an Excel file and that briefly shows approx. 2% CPU usage as well.
 
Why did my Duck just start to use a huge chunk of processor time, and why can''t I access the web page any more?
 
There is a memory-leak bug in the Java code which runs the duck, which requires it to be restarted once every 24 hours to avoid this problem. The software should have installed a helper task that would take care of this, but you can set it up to be a automated task in windows. This is, unfortunately, a bug in the Java runtime environment itself, and beyond our control.
 
Why doesn''t the WxDux need a power supply?
 
It uses two of the serial data lines (DTR and CTS) from the PC as power. The software supplied turns these lines on. Each line can supply 5 VDC @ 5 mA; together, they supply enough power to run the WxDux.
 
How far can the Web Cam be from the PC using the WxDux?
 
16 feet is the USB spec. You can go further using a USB hub.
 
Can I rename the IO sensors on a Duck like I can a goose?
 
NO
 
We have a Duck, how can recover our password on the duck?
 
If you forgot your duck password you will need to uninstall and reinstall the duck software.
 
SENSORS
 
Door Position Magnetic Switch Wiring - One Door Per Input
 

Each door switch goes to an individual I/O port. When a door position is changed, you can tell which door has been opened by viewing the alarm source, IO1, IO2, or IO3. Either Normally Open (NO) or Normally Closed Magnetic Switches can be used, since you are looking for a state change and either type will deliver that; we do, however, recommend that you use only one type of switch so you can more easily keep track of which is closed or open.

Note that there are three ports and only two Common (C) ports; you can use either "C" port as a Common to the I/O ports, and polarity is disregarded in passive devices, so you can connect two door sensors to the same (C) port. Wires up to 200'' can be run. We recommend 22 gauge solid conductor, two wire cable.

 
Door Position Magnetic Switch Wiring - Multiple Door Switches per Analog Input
 

When you need more than three door sensors or you need to put all of your door sensors on one port they may be wired in series. The disadvantage of this is that you will know a door opened, but not which one. In this drawing, three magnetic switches are wired in series. You must use Normally Closed (NC) magnetic switches for this configuration.

Note that an alarm will only indicate which group of door sensors has been opened, but you will not be able to determine which individual door within the group was opened.

 
Water Sensor - One Sensor per Port
 

The water sensor measures conductivity.  No current flows when the sensor is dry, which gives a reading of "99". When water is present, some current flows (the exact amount will depend on the water''s mineral content), which will cause the reading on the I/O port to fall as the resistance across the water-sensor contacts decreases.

 
Water Sensor - Multiple Sensors per Port
 

If you need more than three liquid sensors, you can wire them in parallel in the same manner as door-position switches.  

Note that again, an alarm will only indicate which group of water sensors has become wet, but it will not indicate which individual sensor within the group is wet.

 
My smoke detector is reading differently from what the instructions say it should read, why is this?
 
The smoke detector''s operation was inadvertently described in reverse in some early versions of the instruction sheet. A smoke detector should read high when there is no smoke, and low when the smoke alarm is tripped.
 
How fast will a city power monitor inform me of a power outage?
 
The IO graph on a CPM will slowly fall should there be a loss in power, it may take a few seconds to drop below the normal operating range.
 
How can I calibrate my Airflow sensors?
 

Note: This applies to WxGoos Series I only

When the airflow is reading higher than 20 or so in still air you may need to recalibrate. This can by done by:

  1. Airflow is best detected when the AF sensor''s open end is pointed towards the object of interest. Keeping this in mind, place the AF sensor in a "still air" environment. The AF sensor should be plugged into the powered-on Goose unit. Let the AF sensor sit in the "still air" environment for at least 10 minutes while it collects data. "Still air" is an environment where airflow should be low to nonexistent. This level will then correspond roughly to a reading of 20 on the AF sensor.
  2. Telnet into the Wxgoose device. Check the firmware on your Wxgoose. The firmware is located on the top right corner of the web page. If the firmware is version 2.30 or earlier, use this to login:

    login: admin
    password: mallard

    If your firmware is later than version 2.30 then you must create an administrator account and use that to login to telnet. You can create an administrator account through the ''config'' tab located on the top menu on the web page.

  3. Once you are logged in telnet type in the command ''afcal'' and hit enter. A few messages should come up regarding ''devices found.'' At this point the AF sensor is calibrated, and you may exit the telnet session. The unit now needs to be rebooted for the new calibration to take affect.
 
TEMPERATURE
 
How accurate is my temperature sensor?
 
It is accurate to +/- 0.5°C
 
My temperature sensor is reading high, why is this?
 

To get meaningful temperature measurements, the temp-sensor/measurement system must be accurate, the temp sensor must be located where the temperature needs to be measured, and the temp sensor must be mounted or attached in such a way as to minimize stray thermal conduction.

Temperature sensors have a finite thermal mass, and must be connected to a measurement circuit in a way that permits some thermal conduction between the circuit and the sensor. In addition, most sensors have self-heating which is the heating of the sensor due to the electrical power that the sensor itself dissipates. The temperature rise seen on the MiniGoose is not due to self-heating, it is due to thermal conduction from the web server.

The effect of thermal mass is to delay the response of the sensor to a change in temperature and to filter out any rapid changes in temperature. This is often specified as a thermal time constant which is a measure of the time it takes the sensor to respond fully to a step change in the temperature. The DS18B20 does not specify a thermal time constant but I expect it to be on the order of a minute or more. Attaching the sensor to a circuit board or cable will increase the thermal time constant. The thermal time constant is also a function of the humidity and air speed.

For remote temperature probes, we rely on the manufacturer of the DS18B20 for the accuracy of the sensor (+/-0.5° C over -10-85° C). Because it has a digital output no accuracy is lost in the measurement system (the Goose). By its design, the customer can locate the sensor where they want to measure the temperature. However, there are a few problems that can arise when locating the sensor. First, the cable must be routed to the location of the sensor and because the cable is thermally coupled to the sensor it can act as a heat sink or source for the sensor. This means that if the cable is routed through a hot or cold area, or against hot or cold surfaces, it can affect the temperature readings.

Secondly, the method of attaching the sensor can be critical. If it is attached to a surface or object, the temperature measurements may be more related to the temperature of the surface or object than the surrounding air. In addition, hot-spots (and occasionally cold-spots) can develop, especially inside cabinets. It is best to mount the sensor by clamping the cable some distance from the sensor and using the stiffness of the wire cable to hold the sensor in place. Hanging the sensor has the same effect. Unless the customer specifically wants to measure for hot-spots the sensor should be placed in moving air, preferably air that is being forced to move with a fan.

The internal temp sensor on the Goose and other products suffers from all of the effects mentioned above, but still can be useful for detecting temperature related problems if accuracy and location are not critical aspects of the measurement. Ensuring good air flow across the front of the unit will improve the quality of the internal temperature measurement.

 
Can I place of offset on the sensor to compensate for the heat?
 
You can set a temperature offset for the internal sensor on the Display page.
 
My sensor is off by 8-10°F why is this?
 
our sensor may be defective. Please emailsupport@itwatchdogs.com for RMA''s.
 
POWEREGG
 
What''s the purpose of the Power Egg?
 
There''s no easy way to know how much current a power strip is consuming. The Power Egg plugs in between the power source (wall) and the existing power strip.
 
What does it measure?
 

Peak volts, low volts, amps, watts, power factor and kilowatt-hours consumed.

Volts can range from 100 to 280 VAC (volts AC).

Amperage can go as high as 30 amps but the cables available are only rated for 20 amps.

 
Does the unit operate only from 120 volts?
 
No, the device will operate from 100 to 280 VAC.
 
What kind of connectors does come it with?
 
5-15 is standard. L5-15, L5-20, and 5-20 connectors are optional.
 
Does it operate as a stand-alone unit?
 
Yes, a built-in LCD display with backlighting constantly cycles through the data.
 
How can I log the data?
 
Attach the Power Egg to any IT Watchdogs climate monitoring hardware with RJ-12 port and you can view graphs or download data as an Excel spreadsheet.
 
CURRENT TRANSFORMER (CT)
 
What does a current transducer (CT) do?
 
The CT is an alternating current measurement device. The unit has swing-open jaws that clamp around one wire. The unit is switch selectable for 30,60,120 amps. The output is a DC signal from 0-5V proportional to the current. This device connects to the analog input ports of IT Watchdogs climate monitors. The climate monitor will display a value from 0-99 proportional to both the input voltage and the current measured.
 
How accurate is the current transducer?
 
2%
 
Does it measure voltage?
 
No, just current.
 
Does it matter what the voltage is on the power line?
 
No, typical voltages are 120 to 480 VAC.
 
What''s a typical application of a current transformer?
 
Three phase load balancing. Three current transformers and a Goose provide a low-cost method of balancing the phases. You can also snap current transformers around the wires in a breaker box and measure the current flowing through each breaker. This allows an IT manager to know if any breaker is close to its limit.
 
How many CT''s can a WeatherGoose monitor?
 
Three without additional hardware. However, with a product called the CCAT, more can be added as serial devices, i.e. through the RJ-12 ports.
 
How do I connect the CT? How long can the wire run be?
 
We recommend 22 or 24 AWG solid conductor wire, but any wire close to that should work. Hundreds of feet on a wire run is typical.
 
Are other current ratings available?
 
You can special-order any range up to 300 amps, AC.
 
D-LINK DCS-950 WEBCA
 
How do I connect the camera?
 
  1. Connect the D-Link to a local system with the supplied Ethernet cable.
  2. Power the camera with the power supply that came with the camera.
  3. Make sure both the Power and Link lights are on.
 
How do I install the software for DCS-950?
 
  1. Run the CD that came with the camera.
  2. Select Install Software.
  3. Click on Installation Wizard.
  4. Follow the on-screen instructions to install the software.

DCS-950: During this process a program called ffdshow is installed. Included in the ffdshow files is the video codec required to view the video emails sent by the camera. This codec needs to be installed on all systems where the videos may be viewed, which can be done by installing ffdshow on those systems.

 
How do I set the cameras IP address on the DCS-950?
 
  1. Run the DCS-950 Series SetupWizard. It may take a minute to load.
  2. Click on Wizard to start configuring the camera.
  3. Enter the username and password. The default is admin for both fields.
  4. Select Next to bring up the Set IP Address screen.
  5. Enter the IP address for the camera in the fields.
  6. Click Next when finished.
  7. Select Restart to save changes and wait for the camera to reboot.
  8. In a few minutes the first screen of the setup should show up. Make sure the camera appears in the window on the right and has the correct IP address.
  9. If it doesn''t show up select Search.
  10. If the IP address shown is incorrect then start over at step 2 and try setting the IP again.
 
How do I login to the DCS-950 camera?
 

Internet Explorer 6.x or higher with ActiveX enabled is required to login to the camera. Refer to Enabling ActiveX, the last section of this document, for more information.

  1. Type the IP address of the camera into Internet Explorer.
  2. On the login screen, see if there is a warning at the top, about refusing to download an ActiveX program. Click on this and download it.
  3. Enter the username and password. The default is admin for both.
  4. Click Apply to login
 
How do I update the firmware?
 

To find out what version the camera is running, do the following:

  1. Login to the camera.
  2. Click the setup button.
  3. Select the Status Tab.
  4. Under Server Status is the firmware version number.

    If the firmware version is 1.02 or lower, then the firmware will need to be updated. The following steps will guide you through the update process.
  1. Download the newest firmware at http://support.dlink.com
  2. Login to the camera.
  3. Select setup.
  4. Click on the Tools tab.
  5. Pick firmware from the buttons on the left side of the screen.
  6. Use the browse button to open a Choose File window.
  7. Select the new firmware file, downloaded in step.
  8. Click the Apply button to start the update. This will take several minutes.
  9. The screen will change and give you a Restart option. Select it.
  10. Click the Login button, once the Restart countdown finishes.
  11. Check the firmware version to make sure it updated correctly.
 
How do I set up my camera to email me when it detects motion?
 

The first step is to configure the motion detection settings. The following steps cover the basic setup. Consult the camera manual for additional information.

  1. Login to the camera.
  2. Click on the Setup button.
  3. Select the Tools Tab.
  4. Pick Motion Detection on the left of the screen.
  5. Check the Motion checkbox.
  6. Click on the Zone1-3 buttons to view the motion detection region boxes.
  7. Use the sliders to set the sensitivity and percentage for each region.
  8. Select OpenMSD to preview the motion detected in each region.
  9. Save the settings when done.
  10. Click on Tools to go back to the previous menu.

    Now that the motion detection is configured, the email settings can be entered. Below are the steps needed to setup email.
  1. Select Trigger on the left side of the screen.
  2. Check the By Email checkbox.
  3. If a username and password is needed, fill in these fields and check the checkbox next to them.
  4. Fill in the remaining input fields.
  5. You can select Test to test the configuration, but it still may work even if the test fails.
  6. Click on Apply to save the changes.

If the camera detects enough motion to trigger an alarm it will send an email to the set email address. Then the camera waits for a certain period of time before it can detect and send another email. This wait period is controlled by the Motion Detection Skip Set Time input field.

To test the configuration, wave something in front of the camera to set off the motion detection. Wait a few moments and check the appropriate email address for an alert email from the camera

 
I see the Login page, and enter the correct username and password, but when I select Apply nothing helps.
 
An ActiveX application is required to access the camera and will only work with Internet Explorer 6.x and higher. Make sure the IE is not blocking this program from being installed. Allow the camera to install the DLink program if asked by the browser.
 
The SetupWizard shows that the IP address of the camera was set, but I can''t access it with my browser.
 
Make sure the network card setting are correct for the camera IP address you are trying to reach.
 
I can access the camera with Internet Explorer, but the Goose doesn''t get a picture from the camera.
 
Check the Camera IP address and camera model in the Goose Configuration. If the configuration looks correct, then make sure the camera is running a firmware version 1.03 or higher. If necessary, download the newest firmware from support.dlink.com and update the firmware on the camera.
 
How can I enable ActiveX only for the WxGoos?
 

To setup the DLink camera, ActiveX must be enabled. Depending on the Internet Security settings, ActiveX is normally enabled. However, some consider ActiveX to be too much of a security risk and disable it. A way around this is create a list of trusted sites and enable ActiveX for those sites only. Below are instructions for both enabling ActiveX for all sites and just for the Trusted sites. Consider the security risks before changing the security settings.

Security Settings to Medium

Enabling ActiveX for Trusted sites:

  1. Open Internet Explorer.
  2. Click on Tools in the menu bar.
  3. Select Internet Options.
  4. Select the Security Tab.
  5. Make sure that the Internet icon is selected.
  6. If the security is set to Medium, then ActiveX is enabled and the camera should work. If the setting is something else, then click Default and you should see the level change to Medium. Refer to figure 1.
  7. Click the OK button at the bottom of the screen to save the changes


Changing Settings for Trusted Sites

Enabling ActiveX for all sites:

  1. Open Internet Explorer.
  2. Choose Tools from the menu.
  3. Select Internet Options.
  4. Select the Security Tab.
  5. Click on the Trusted Sites icon.
  6. Move the security slider to the left to Medium. If there is no slider then click on Default Level to get one. This can be seen in Figure 2.
  7. In the middle of this window and to the right is the button Sites. Select it.
  8. Uncheck "Require server verification (https:) for all sites in this zone".
  9. Enter the IP address of the DLink in the first input field.
  10. Click Add to put the camera IP in the list of Trusted sites. Refer to Figure 3.
  11. Select OK to close this window.
  12. Click OK at the bottom of the Security page to save the settings.


Adding Camera IP to Trusted Sites List

 